VAV-PRC011M-EN 145
Application Considerations
Currently, VariTrane offers two models of pneumatic volume regulators in its controls offering—
the 3011 regulator (used in most applications) and the 3501 model (used in dual-duct constant-
volume applications). The primary difference is the 3501 PVR’s ability to change the velocity
pressure linearly with a change in thermostat pressure, which results in improved stability at low
flows. In contrast, the 3011 PVR resets the velocity pressure with a change in thermostat pressure.
Reset Control of Minimum and Maximum Flow—The 3011 PVR and 3501 use fixed reset control of
minimum and maximum flow settings. The primary benefit of fixed reset in a pneumatic volume
regulator is stable flow control without excessive damper movement.
Fixed Reset—A fixed reset controller operates over a thermostat signal change of 5 psi between
minimum and maximum flow, regardless of the differential pressure flow sensor signal. The
thermostat is usually set for a gain of 2.5; i.e. it produces a 2.5 psi output change per degree of space
temperature change. This control strategy provides stable flow control with the primary air valve
throttling between minimum and maximum flow over a 2°F space temperature change.
Example 1: Air valve with a 6" inlet, Pneumatic thermostat gain = 2.5 psi/degree:
Minimum Flow=0 cfm, 0.0 in. wg flow signal
Maximum Flow=680 cfm, 2.0 in. wg flow signal
2.0 in. wg signal range
The damper will modulate from zero to maximum position over a 2°F temperature change.
Bleed Port to Atmosphere—Bleeding air to the atmosphere is a normal operation for a volume
regulator. The 3011 volume regulator addresses this function with a dedicated bleed port. When air
is bled through the flow sensor, the differential pressure signal from the sensor is affected. As a
result, the flow sensor signal can be radically altered if the volume regulator is bleeding air, and
may cause excessive damper movement.
Calibration—The minimum and maximum settings are independent of each other and need to be
set only once during calibration.
Signal Configuration Flexibility—Both can be configured to work with both normally-open and
normally-closed pneumatic air valves, and both direct-acting and reverse-acting thermostats.
Pneumatic Volume Regulators