Pneumatic Controls
3501 Pneumatic Volume Regulator
This is in contrast to the 3011 PVR, which resets velocity pressure with a change in thermostat
pressure. This allows the 3501 PVR to have improved stability at low flows.
Specifications
Differential Pressure Range
0–1.0 in. wg (0–249 Pa)
Minimum Setpoint Range
0–1.0 in. wg (0–249 Pa)
Maximum Setpoint Range
Minimum to 1.0 in. wg (249 Pa)
Operating Static Pressure Range
0.25–6.0 in. wg (62.3–1494 Pa)
Reset Pressure Span
Factory-set at 5 psig (34.5 kPa)
Field-adjustable from 0 to 7 psig
(0 to 48.3 kPa)
Reset Start Point
Factory-set at 8 psig (55.2 kPa)
Field-adjustable from 0 to 10 psig
(0 to 68.9 kPa)
Main Air Pressure
15–30 psig (103 to 207 kPa)
Air Consumption
43.2 scim (0.708 L/m) at 20 psig (138 kPa) main air pressure
Operating Environment
40 to 120ºF (4 to 49°C)
Storage Environment
-40 to 140ºF (-40 to 60°C)
Output Sensitivity
5 psig/ 0.02 in. wg (34.5 kPa/ 5.0 Pa)
Physical Dimensions
Width: 4.5" (114.3 mm)
Length: 3.87" (98.3 mm)
Tubing Connections:
1/4" O.D. tubing connections
The 3501 PVR can be set to control either normally open or normally-closed
air valve actuators and can be calibrated to accept either direct-acting or
reverse-acting thermostat signals. Fixed reset control of maximum and
minimum airflow setpoints is provided. The controller is used primarily in
dual-duct constant-volume applications because of its linear output
response characteristics. The controller resets the primary air velocity
linearly with a change in thermostat pressure.