VAV-PRC011M-EN 111
DDC Controls
VAV Piping Package
Specifications
Differential Operation Pressure:
• 2519 (2-80 psid 0.5-3.0 gpm) / (3-80 psid 3.50 – 5.00 gpm)
• 2515 (3-80 psid 5.50 – 9.00 gpm)
• 2524 (3-80 psid 10.0 –17.0 gpm) / (5-80 psid 18.0 –23.0 gpm)
• ± 10% accuracy of published flow
Operating Temperature:
32° - 225°F
• Offered in both 2-way and 3-way configurations
• The Automatic Balancing Flow Control sized for the specified VAV coil
and gpm.
• Field connections are NPT with Coil connections Sweat to match the
Trane VAV water coil copper
• For 3-way configuration the connections between the ATC valve and the
supply shut off assembly are sweat to allow for field installation of hose
or piping connection between the supply and return lines.
• Included in the package are:
• P/T Ports for pressure and temperature measurement on both the
supply and return sections.
• Blow down drainable filter on the supply.
• Y-Ball Combination Mesurflo Automatic Balance Valve on the Return
side to isolate the coil
• Y-Ball Combination Strainer on the supply to isolate the coil.
• Each piping package is tagged to match the VAV terminal tag it is
specified for.
• Each piping package includes a 24v floating point control proportional
control ball valve.
• The Cv is sized to match the specified gpm/coil performance of the VAV
terminal unit. Package includes unions with sweat connections to the
coil.
Komentáře k této Příručce