T-Stat Branch Pressure (kPa)
T-Stat Branch Pressure (PSI)
Heating
% Position (Open)
3
8
Cooling
100
20.7
55.2
13 15
100
89.6
103.4
8 PSI Out
(55.16 kPa)
(55.16 kPa)
8 PSI In
Relay
Reversing
B
S
M
Tee
Optional or installed by others.
Factory installed.
Customer Notes:
1.
Remote Mounted
Two Pipe
T-Stat
(Reverse Acting)
Restrictor
Tee
Restricted Leg
One Pipe Inset
One Pipe
Remote Mounted
(Reverse Acting)
T-Stat
Actuator
Actuator
(Direct Acting)
Remote Mounted
One Pipe Inset
Optional or installed by others.
CoolingHeating
Cooling
T-Stat Branch Pressure (PSI)
T-Stat Branch Pressure (kPa)
3
8
55.2
20.7
CFM
% Flow (CFM)
Min
CFM
Max
100
Heating
1. Factory installed.
1513
(Direct Acting)
T-Stat
Two Pipe
Remote Mounted
Customer Notes:
103.4
89.6
100
Max
LPS
Min
LPS
% Flow (LPS)
One Pipe
Restrictor
Tee
Restricted Leg
T-Stat
B
M
Flow Ring
Actuator
Heating
LO
HI
Cooling
Flow Ring
Actuator
Regulator
Volume
H
L
T
LO
HI
M
B
H
L
T
With an increase in room temperature, the thermostat pressure is decreased. The cooling valve actuator opens the damper to
increase primary cooling flow to the space, the heating valve is closed. With a decrease in room temperature, the heating valve
modulates and the cooling valve is closed.
% Position (Open)
20
(137.9)
S
20
(137.9)
S
20
(137.9)
S
(137.9)
S
20
S
(137.9)
20
S
(137.9)
20
S
(137.9)
20
Volume
Regulator
(Normal Operation: Cooling and Heating)
Normally-Open Heating Damper with Actuator and Normally-Open Cooling Damper with Actuator
(Reverse-Acting Thermostat)
PN08 – VDDF - Dual-Duct Terminal Units
PN09 – VDDF - Dual-Duct Terminal Units
(Normal Operation: Cooling and Heating)
Normally-Open Heating Damper with Actuator, Normally-Open Cooling Damper with Actuator, and
3001 Pneumatic Volume Regulator (Qty of 2) (Direct-Acting Thermostat)
With an increase in room temperature, the thermostat output pressure is decreased. This signal is input to the volume regulator,
which also receives the inputs from the high- and low-pressure from the flow ring. The volume regulator outputs a signal
compensated for changing duct pressures to the valve actuator, which opens the damper and increases primary cooling flow to the
space. With a decrease in room temperature, the opposite action occurs. Minimum and maximum primary airflow settings are
maintained by the volume regulator. If the zone temperature continues to decrease after the fan has been energized, heating stages
are energized at the appropriate pressure settings.