
Installation - Mechanical
CXRC-SVX01F-EN 15
Leveling the Unit
Before tightening down the mounting bolts, level the unit
carefully. Use the unit base rail as a reference. Level the
unit to within ¼” over its entire length. Use shims if
adjustable isolators are not used.
Refrigerant Piping
General Refrigerant Recommendations
Liquid Line Components
Indoor portion of liquid line should include service valve,
charging valve, thermal expansion valve, sight class/
moisture indicator, filter drier and solenoid valve. (Others
as required by job specifications.) If the CCRC/CIRC is
coupled with either SCRF/SIRF or SCRG/SIRG, these
components are factory installed in the indoor unit, except
filter driers which are ship-with, for field installation.
CCRC/CIRC units also include a charging valve.
• Sight glass/moisture indicators aid in troubleshooting,
charging and servicing the system. Locate between
filter drier and expansion valve.
• Filter-driers are provided for field installation. Locate
near evaporator.
• Solenoid valves should be located near the evaporator.
Discharge Line Components
Indoor portion of discharge line should include access
valve and check valve. If the CCRC/CIRC is coupled with
either SCRF/SIRF or SCRG/SIRG, these components are
factory installed on the indoor unit. Install other discharge
line components as required by job specifications (hot gas
mufflers, pipe anchors, oil traps, etc.) to provide proper
system operation, prevent excessive vibration and assure
proper oil return to the compressor. Also recommended
are discharge shutoff valves in each hot gas line near the
condenser to facilitate refrigerant storage in the
condenser during service procedures. When optional
discharge line ball valves are present in the indoor section,
installation of field supplied discharge line access valves
near the indoor unit may aid in installation and service.
Note: See Figure 17, p. 16 for a typical refrigerant piping
configuration that may be used in place of a double
riser system (not recommended).This
arrangement assures adequate oil return to the
suction line, even at partial load conditions. Refer
toTrane Reciprocating Refrigeration Manual for
more specific piping recommendations.
Figure 14. Isolator locations for CCRC/CIRC 20-32 tons
Figure 15. Isolator locations for CCRC/CIRC 35-40 tons
Figure 16. Isolator locations for CCRC/CIRC 50-60 tons
NOTICE:
Compressor Damage!
To prevent possible refrigerant drain back into
compressor during off cycle, if no discharge check valve
is used, drop discharge line well below compressor
discharge level before beginning vertical rise. Failure to
do so could cause compressor damage.
Komentáře k této Příručce