Dimensions and Weights
10 CXRC-SVX01F-EN
Service Clearances
Provide sufficient clearance around the unit to allow
unrestricted access to control panel, condenser coils,
refrigerant connections and any other service points. Refer
to Figure 2, p. 9 through Figure 4, p. 9 for unit dimensions
and Figure 6, p. 11 through Figure 8, p. 11 for
recommended clearances for each specific unit.These
clearances allow for proper unit operation, airflow, and
service access and should not be infringed upon.
Note: To prevent unit capacity reduction, be certain to
provide recommended operating clearances.
If unit is installed in a pit, the depth of the pit must not
exceed 1.5 times the unit height and airflow clearances are
doubled. See Figure 10, p. 11 for specific pit installation
clearance instructions.
If multiple units are placed side-by-side, the minimum
distance between units must be twice the normal
recommended side clearances (8X2=16feet between
units). See Figure 11, p. 12 for specific side by side
installation clearance instructions.
Do not install unit under an overhang. Obstructing the fan
discharge in this manner can cause recirculation of the
warm discharge air and result in coil starvation.
Table 3. CCRC/CIRC unit dimensions, inches (mm)
Unit Tons AA AB AC
CCRC/CIRC
20, 29, 32
70 1/8 7' - 4 7' - 4
(1781) (2235) (2235)
CCRC/CIRC
35, 40
70 1/8 10' - 10 3/4 7' - 4
(1781) (3321) (2235)
CCRC/CIRC
50, 60
70 1/8 14' - 8 7' - 4
(1781) (4470) (2235)
Table 4. CCRC/CIRC unit weights
Unit
Size
Shipping
Weight lbs (kg).
Operating
Weight lbs.(kg)
CCRC/CIRC 20 2030 (920) 1906 (865)
CCRC/CIRC 29 2084 (945) 1960 (890)
CCRC/CIRC 32 2138 (970) 2014 (915)
CCRC/CIRC 35 3018 (1370) 2833 (1285)
CCRC/CIRC 40 3072 (1395) 2887 (1310)
CCRC/CIRC 50 3995 (1810) 3695 (1675)
CCRC/CIRC 60 4275 (1940) 3975 (1805)
Figure 5. Refrigerant and electrical connections (front view looking at control panel)
(a)
(a) See Table 6, p. 16 for refrigerant connection and piping sizes.
B
C
(LIQUID LINE CONNECTION REFRIG. CIRCUIT 1)
(HOT GAS CONNECTION REFRIG. CIRCUIT 1)
(LIQUID LINE CONNECTION REFRIG. CIRCUIT 2)
(HOT GAS CONNECTION REFRIG. CIRCUIT 2)
REFRIGERANT CIRCUIT 2
REFRIGERANT CIRCUIT 1
24 VOLT WIRE ENTRY HOLE
SIZED FOR 3/4” CONDUIT
115 VOLT WIRE ENTRY HOLE
SIZED FOR 3/4” CONDUIT
SUPPLY VOLTAGE WIRE ENTRY
HOLE SIZED FOR 1” CONDUIT
66 7/8” (1699mm)
18 1/2” (470mm) - Hot Gas Conn Refrig - ckt 1
4 1/2” (114mm)
10 1/2” (261mm)
17 1/2” (445mm)
14 3/8” (365mm) - Liq Line Conn Refrig - ckt 1
24 3/4” (629mm) - Liq Line Conn Refrig - ckt 2
29” (737mm) - Hot Gas Conn Refrig - ckt 2
Refrigerant Circuit 1
Refrigerant Circuit 2