34 VRF-SVN33A-EN
Refrigerant
Refrigerant
After successful leak testing and vacuum drying, calculate the amount of refrigerant needed and
then charge the system, as explained in this section.
Calculating the Refrigerant
The initial refrigerant quantity (given in Table 15) is charged into the unit at the factory.
Calculate the total amount of additional refrigerant to add to the system as follows:
Total additional refrigerant = [total length of 3/8 in. (0.52 mm) liquid piping x 2.12 oz (60 g)] + [total
length of 1/4 in. (6.35 mm) liquid piping x 0.71 oz (20 g)] + [total refrigerant quantity for all
connected indoor units (refer to Table 16)].
Table 15. Initial refrigerant quantity for each mini outdoor unit model
Model
4TVH0036B100NB (3 ton) 4TVH0048B100NB (4 ton) 4TVH0053B100NB (5 ton)
Initial refrigerant
quantity: lb (kg)
7.1 (3.2) 7.1 (3.2) 7.3 (3.3)
Table 16. Refrigerant quantity for each indoor unit
Capacity (MBH)
7. 5 9 9.5 12 18 20 24 30 36 48 76.8 96
Model
Refrigerant quantity: lb (kg)
1-way cassette
(4TVE00**B100NB)
0.55
(0.25)
0.55
(0.25)
0.55
(0.25)
Mini 4-way cassette
(4TVB00**B100NB)
0.82
(0.37)
0.82
(0.37)
0.82
(0.37)
0.82
(0.37)
4-way cassette
(4TVC00**B100NB)
0.99
(0.45)
0.99
(0.45)
0.99
(0.45)
1.52
(0.69)
1.52
(0.69)
1.52
(0.69)
Slim duct
(4TVL00**B100NB)
0.53
(0.24)
0.53
(0.24)
0.53
(0.24)
0.99
(0.45)
0.99
(0.45)
0.93
(0.42)
0.93
(0.42)
1.37
(0.62)
MSP duct
(4TVD00**B100NB)
0.62
(0.28)
0.62
(0.28)
1.19
(0.54)
1.19
(0.54)
1.50
(0.68)
HSP duct
(4TVA00**B100NB)
1.50
(0.68)
1.50
(0.68)
2.60
(1.18)
2.60
(1.18)
High-wall
(4TVW00**B100NB)
0.53
(0.24)
0.53
(0.24)
0.53
(0.24)
0.79
(0.36)
0.79
(0.36)
0.79
(0.36)
Convertible
ceiling/floor
(4TVX00**B100NB)
0.86
(0.39)
0.86
(0.39)
Komentáře k této Příručce