Refrigerant Piping
Nitrogen Flushing While Brazing
While brazing refrigerant pipes, flush them with nitrogen gas. Use a pressure regulator to maintain
a flow rate of 1.76 ft
3
/h (0.05 m
3
/h) or more.
Figure 13. Nitrogen flushing while brazing refrigerant pipes
Flared Pipe Connections
Clutch type and wing nut type flare tools are available for flared pipe connections.
1. Slide the flare nut over the pipe to be flared.
2. Slide the end of the pipe into the hole on the flaring bar that fits the pipe, leaving a length of
pipe, determined by tool type (see table), extending above the flaring bar. Clamp it down.
NOTICE
Avoid Unit Damage!
Never braze pipe connections without performing nitrogen flushing. Failure to perform this
procedure will damage the unit, resulting in capacity loss and reduced long-term reliability.
Flow meter
Pressure regulator
Stop valve
Nitrogen
Nitrogen
R-410A clutch type
Conventional flare tool
Clutch type Wing nut type
0–0.020 in. 0.04–0.06 in. 0.06–0.08 in.
Length of pipe extending above flare bar
Pipe
Flaring
bar