Operation
GUNE-SVX001A-EN 29
Tubular Duct Furnace—High Altitude
Deration
This tubular duct furnace has been manufactured utilizing
standard burner orifices and a normal manifold pressure
setting as per the specifications shown on your unit rating
plate.
All unit deration must be done through field adjustments
by a qualified technician. Once the proper adjustments are
made in the field, attach label #J17-06459 to the unit, and
record adjusted manifold pressure, altitude of the unit
installation, the technician’s name, and the date on the
label using a permanent marker.
Refer to Adjusting Gas Pressure,” p. 28 for adjusting the
manifold pressure.
Table 10. High altitude deration—United States
Altitude
Manifold Pressure
BTU Output
(a)
Natural Gas
(b)
Liquid Propane
(c)
Feet Meters Inches wc Pa Inches wc Pa Percentage
0–2,000 0–610 3.5 872 10.0 2491 100%
2,001–3,000 611–915 3.2 797 9.2 2292 96%
3,001–4,000 916–1,220 2.9 722 8.4 2092 92%
4,001–5,000 1,221–1,525 2.7 673 7.7 1918 88%
5,001–6,000 1,526–1,830 2.4 598 7.0 1744 84%
6,001–7,000 1,831–2,135 2.2 548 6.4 1594 80%
7,001–8,000 2,136–2,440 2.0 498 5.7 1420 76%
8,001–9,000 2,441–2,745 1.8 448 5.1 1270 72%
9,001–10,000 2,746–3,045 1.6 399 4.6 1145 68%
Note: Consult local utility for actual heating value.
(a)Deration based on ANSI Z223.1 (NFPA 54).
(b)Table based on heating value of 1,050 Btu/ft
3
at sea level.
(c) Table based on heating value of 2,500 Btu/ft
3
feet at sea level.
Table 11. High altitude deration —Canada
Altitude
Manifold Pressure
BTU Output
(a)
Natural Gas
(b)
Liquid Propane
(c)
Feet Meters Inches wc Pa Inches wc Pa Percentage
0–2,000 0–610 3.5 872 10.0 2491 100%
2,001–3,000 611–915 3.2 797 9.2 2292 96%
3,001–4,000 916–1,220 2.9 722 8.4 2092 92%
4,001–5,000 1,221–1,371 2.8 697 7.9 1968 90%
Note: Consult local utility for actual heating value.
(a)Deration based on CGA 2.17-M91.
(b)Table based on heating value of 1,050 Btu/ft
3
feet at sea level.
(c) Table based on heating value of 2,500 Btu/ft
3
at sea level.