CLCH-PRC016-EN 21
Service Clearance Recommendations
A minimum clearance of the section width plus 12 inches on the access door side of the gas heat
section is recommended for routine maintenance. This clearance provides enough room to replace
the heat exchanger in the event of failure. The section side panels must be removed to access the
heat exchanger. Refer to Figure 1 for service clearance recommendations for the air handler.
Figure 1. Service Clearance
Filter mixing box
Coil
Fan
Gas heat
Access
door
UV
lights
VFD
F
E
D
C
B
A
Table 9. Service clearance dimensions (inches)
Component 3 4 6 8 10 12 14 17 21 22 25 26 30 31 35 36 40 41 50 51 57 58 66 80 100 120
A (filter) 4848484848484848484848484848484848484848484852565858
B (coil) 48 59 59 66 77 82 87 87 95 77 95 77 109 87 115 96 128 96 141 110 141 110 156 156 170 197
C (UV Lights) 4848484848484848484848484848484848484848484852565858
C (Catalytic Air
Cleaner)
43 59 59 63 75 81 83 83 58 75 58 75 83 83 75 59 83 83 83 83 83 83 83 83 75 83
D (external starter
or VFD)
61 61 61 61 61 61 61 61 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64
D (internal starter
or VFD)
48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48
E (fan) 484848485154586160516651665866607060776677669393101101
F (gas heat - Ext
Vestibule)
n/a n/a 89 90 108 100 100 105 115 n/a 115 n/a 118 n/a 136 n/a 140 n/a 156 n/a 156 n/a 170 179 180 n/a
F (gas heat - Int
Vestibule)
n/a n/a 56 63 74 79 84 84 92 n/a 92 n/a 106 n/a 112 n/a 125 n/a 138 n/a 138 n/a 153 153 167 194
Note: At a minimum, the above clearance dimensions are recommended on one side of the unit for regular service and maintenance. Refer to as-built
submittal for locations of items such as filter access doors, coil, piping connections, motor locations, hoods, pipe cabinets, etc. Sufficient clearance
must be provided on all sides of unit for removal of access panels, plug panels, or section-to-section attachment brackets. Clearance for starters, VFDs,
or other high-voltage devices must be provided per NEC requirements.
Note: For specific dimensional and weight information, refer to the unit submittals. The dimensions and weights in this manual are approximate. Trane has
a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.