Assembly and Installation
7. Install gasket along the perimeter of the pipe chase roof curb and unit roof curb. Gasketing is
provided with the roof curb when ordered from Trane.
8. Install the curb. The curb may be set on structural framing (by others). This curb is designed
to transfer the load to a continuous underlying structural frame. The structural members (by
others) should span the perimeter of the curb.
9. Complete all ductwork, piping, and electrical connections only after mounting the unit. Refer
to unit submittals.
Figure 15. Pipe cabinet roof curb assembly
Unit roof curb
2 x 4 nailer
Pipe chase
roof curb
Roof curb
angle